Automated Logic® WebCTRL®’s open architecture and support for industry standards facilitate integration with third-party building mechanical and electrical subsystems. The WebCTRL system is capable of supporting multiple protocols over a TCP/IP network, allowing many items of equipment to connect directly to the WebCTRL Backbone.
Equipment using BACnet can be connected to an IP, ARCNET, MS/TP, or Point-to-Point (PTP) network segment. Our open systems integration allows for seamless interconnection with equipment using BACnet, Modbus®, N2®, JBUS, or LonWorks®, as well as an extensive list of proprietary protocols.
List of integration applications
Electric Meters: Cutler-Hammer®, Electro Industries, GE® PQM, Power Measurement, United Power®, Veris Industries®, ASCO®, APC®, MGE®, Siemens®, Square D®, Setra® Systems, Schneider® ION, Leviton® Series Static Transfer Switches and Switchgear: ASCO®, Cyberex®, GE® Fanuc®, Power Paragon, Zenith®, Russelectric®, Cummins®, LayerZero®, MGE, United Power Computer Room Air Conditioning Units: Air Technology Systems®, Inc. (ATS), APC Network Air, Liebert®, Stulz®, Data Aire® Variable Speed Drives: ABB®, Allen-Bradley®, Cutler-Hammer, Danfoss®, Graham, Square D, Toshiba,® Yaskawa®, Eaton ®, ACH Lighting: GE, Square D, Philips®, Cooper Controls, PCI®, Watt Stopper®, Blue Ridge Technologies® Boilers: Cleaver Brooks®, Fireye®, Lochinvar®, Weil‑McLain®, Grundfos®, Laars,® Reimers® Electra Steam Chillers: Carrier®, Dunham-Bush®, Mammoth®, McQuay®, Trane®, York®, Multistack®, ClimaCool® Fire Systems: Edwards® EST3, Siemens® Fire Finder, Simplex®, Kidde®, Honeywell® Notifier Fume Hood Control: Phoenix, Laboratory Control Systems, Tek-Air, TSI®, Triatek® Generators: Caterpillar®, Cummins®/ Onan, Mammoth, Detroit Diesel®, Kohler® UPS Monitoring: MGE, Powerware®, APC®, Liebert, Piller®)
· Time-lapseTM Graphics
The revolutionary Time-lapseTM feature in the WebCTRL system allows the operator to go back in time, in segments up to 24 hours, and replay real-time hourly data in minutes. You can view floor plans, equipment graphs, trends and alarms from past periods, to quickly identify, review and resolve building control issues.
· Designed for Speed
The WebCTRL system is built for speed. From the high-speed trending engine that can read 860,000+ samples per second on BACnet over the ARCnet network at 156 kbaud, our industry-leading data performance gives you the speed you need to perform critical analysis, reporting, visualizations and digital control presentations.
· Optimal Start and Demand Limit
Optimal start routines and built-in demand limiting work in tandem, shutting down equipment when not required or relaxing setpoints to reduce energy usage while maintaining comfort levels. These are standard features for all WebCTRL systems.
· Unlimited Users
The WebCTRL system is designed to serve an unlimited number of users simultaneously. Multiple licenses are not required, allowing all authorized building personnel to access and control HVAC, lighting, central plant, and other critical systems from on-site or remotely.
· Live Logic
All WebCTRL systems support live visual displays of control logic, which use real-time operational data and help optimize and troubleshoot system operations. There is no need to understand confusing computer code “line by line”
· Environmental IndextmTM
Since the key component in comfort is temperature, the Environmental IndexTM tool assigns score values based on the difference recorded between the area temperature and the heating and cooling set points allowing an overall “score” to be calculated. Other factors such as humidity and CO2 levels can also be considered.
· Request-based control
Integrated request-based control saves energy by ensuring that equipment only runs when occupants are in the building area. This standard feature of the WebCTRL system results in superior occupant comfort and proven energy savings.
· Fault Detection and Diagnostics (FDD)
The WebCTRL system's Automated Logic Fault Detection and Diagnostics (FDD) library can locate over 100 proven faults in typical HVAC equipment, including VAV systems, air handlers, fan coil units, fan unit, water supply heat pumps, and air supply heat pumps.
· All engineering tools
When you purchase a WebCTRL system from Automated Logic, you receive the complete set of tools you need to create your installation. All elements of the product are open and available so that the customer can fully own the system.
· Intuitive user interface
All WebCTRL systems enable robust, comprehensive building management through intuitive, point-and-click navigation. High-definition, factory-generated graphics are included with every WebCTRL system installation, providing a consistent, excellent user experience.
Niagara 4 - Open Performance
From buildings and data centers to manufacturing systems and smart cities, the Niagara Framework improves strategic decision making, enabling performance optimization and cost reductions that can help businesses become more competitive and profitable.
Key Features and Functionality
Intuitive User Interface
Niagara 4 features a bold and intuitive new interface.
Modern and easy to use, the platform uses HTML5
to provide a variety of features.
More Data at Your Fingertips
Integrators can provide an interface that empowers
users to do more on their own. Because devices,
systems, and data points can be tagged in Niagara 4,
users can easily perform a station-wide search for
the most important elements in their operation.
Powerful Security
Niagara 4 takes a “defense in depth” approach to
Internet of Things security. Niagara 4 makes
user permissions completely configurable and easy
to assign.
Application and Use
The iSMA-B-J8 is a compact, embedded IoT controller (JACE 8000) and server platform for connecting multiple and diverse devices and subsystems. With Internet connectivity and web server capability, the JACE 8000 controller provides integrated control, monitoring, data logging, alarming, scheduling, and network management. It transmits data and rich graphical views to a standard web browser via Ethernet or wireless LAN, or remotely over the Internet. The licensing model for the JACE 8000 controller is simplified and features standard controllers along with optional I/O and fieldbus expansion modules for maximum flexibility and expandability.
The JACE 8000 controller runs on Niagara 4, the latest version of the Niagara Framework®, for optimal performance. In larger installations, multi-building applications, and large-scale control system integrations, Niagara 4 supervisors can be used with JACE 8000 controllers to aggregate information, including real-time data, history, and alarms, to create a single, unified application.
Features
• Niagara 4.1 and later
• Real-time clock
• 2 isolated RS485 ports with selectable polarization and termination
• 2 FastEthernet ports
• Optional expansion modules
• Support for a wide range of protocols: LON, BACnet, KNX-IP,
Modbus, M-Bus, SNMP, Z-Wave and others
• Real-time data, history and alarms
• Removable microSD card with total 4GB flash storage/2GB
user storage
• Complete device network management based on
LONworks technology
• Embedded web server, providing a graphical user
interface available from a web browser level
• Different licensing models for various types of applications
Application and Use
iSMA-B-MAC36NL is a compact application master controller with different types of built-in I/O, powered by Niagara Framework.
Using the specific local I/O set (16 UI, 8 AO, 4 DI and 8 DO) allows users to use the device in different applications. The controller provides control, data logging, alarming, programming, integration and visualization.
To enable IP connectivity, there are 2 Fast Ethernet ports that can operate as two independent ports. The built-in RS485 interface can be used to expand the number of I/O by connecting I/O modules from the iSMA-B-MINI or iSMA-B-MIX series or to integrate with other subsystems. There are two further hardware versions of the controller with the second RS485 port or M-Bus interface available.
iSMA-B-MAC36NL provides a rich graphical interface for display in a standard web browser or on an external display connected to built-in HDMI and USB port (touchscreen compatible).
Features
• Niagara 4.4 and above
• Real-time programming
• 2 Fast Ethernet (standalone)
• RS485 port (opto-isolated)
• Second RS485 port (opto-isolated, optional hardware)
version)
• M-Bus interface (optional hardware version)
• 2 USB ports (support for touch screen, mouse, keyboard)
• 16 UI, 8 AO, 4 TU and 8 TU
• HDMI for connecting to an external display
• Embedded web server provides a graphical user interface
available from a web browser level
• SD card for collecting real-time data, history and alarms
• Hardware replacement by SD card
Application and Use
The iSMA-B-AAC20 is an advanced control device for building automation and HVAC systems. Using SVM (Sedona Virtual Machine) allows the user to program quickly and easily in real time. Large number of inputs and outputs allows integration with other devices and sensors (AAC20 provides 8 UI, 4 DI, 4/6 AO and 4 DO). Fully programmable and readable LCD can be used as a simple interface for local operation of the system. The integrated RS485 can be used to expand the number of I/O by connecting MINI or MIX series I/O modules using Modbus RTU/ASCII.
Additionally, to increase the versatility of the controller, it supports many open communications protocols: BACnet, Modbus, SOX, DALI, M-Bus, 1-Wire or oBIX.
The AAC20 is mounted in a housing adapted for DIN rail mounting or directly on a panel. Separate, easy-to-remove connectors allow for quick wiring without removing the entire module.
Features
• Sedona Framework 1.2 support
• Real-time clock (RTC)
• 2 Fast Ethernet with built-in switch
• RS485 port (Modbus or BACnet)
• Built-in LCD display (optional)
• Micro SD card slot for logging historical data and alarms
• Fast processor with dual core 204MHz ARM
• Built-in Modbus TCP/IP to RS485 gateway
• DALI interface – built-in power supply (optional)
• M-Bus interface – up to 20 devices (optional)
• 1-wire interface
• iC Tool – free programming software
• Web-based configuration
• Built-in display web server
The OptiFlex router routes BACnet messages between the WebCTRL building automation system backbone (BACnet/IP) and a subnet of WebCTRL controllers (BACnet MS/TP and/or BACnet ARCnet). It connects directly to the Ethernet LAN and provides the WebCTRL server with access to the entire WebCTRL system.
Key Features and Benefits
· Provides BACnet routing between supported BACnet communication types
· Native high-speed BACnet communications over ARC156 delivers high-speed response when you need it
· Supports up to 99 ARCnet controllers and 60 BACnet MS/TP controllers to connect together over the WebCTRL building automation system backbone
· Two additional BACnet ports to support two simultaneous BACnet MS/TP networks (up to 60 controllers each) or one ARCnet network (up to 99 ARCnet controllers) and one BACnet MS/TP network (up to 60 controllers)
· Can serve as a BACnet Broadcast Management Device (BBMD) that routes any BACnet broadcast message directly to other BBMD devices on the BACnet network
· Supports BACnet Foreign Device Registration (FDR)
· Seamlessly connects to the WebCTRL building automation system.
· Multiple IP ports for local access and network connections
· Multiple serial communication ports for simultaneously routing and sharing data across a wide range of building subsystems.
Hardware Features
· Supports Gig-E addressing, 1000Mbps BACnet IP, and DHCP IP
· Locally accessible 10 or 100 Mbps Ethernet port for system startup and troubleshooting
· Firmware upgrades can be performed remotely
· Capacitor-backed real-time clock maintains time in the event of a power outage or network interruption for up to three days
· Available with DIN rail mounting and screw mounting.
The OptiFlex BACnet Integrator supports routing between multiple BACnet networks. It also supports custom control programs to easily integrate with third-party BACnet equipment such as variable speed drives, boilers, and lighting.
BACnet Features and Benefits
Supports routing between BACnet/IP, BACnet/Ethernet, BACnet ARCnet, and BACnet MS/TP networks
Supports up to 1,500 third-party BACnet points
Supports up to two BACnet/IP networks on the Gig-E port
Includes two additional BACnet ports to support two simultaneous BACnet MS/TP networks (with up to 60 controllers each), or one ARCnet network (with up to 99 ARCnet controllers) and one BACnet MS/TP network (with up to 60 controllers)
Can serve as a BACnet Broadcast Management Device (BBMD), routing any BACnet broadcast message directly to other BBMD devices on the BACnet network
Supports BACnet Foreign Device Registration (FDR).
Hardware Features
· Supports and executes control programs.
· Supports Gig-E, 1,000 Mbps BACnet IP addressing, and DHCP IP addressing
· Ethernet port provides local access for system commissioning and troubleshooting
· Supports network captures for advanced diagnostics
· Provides network statistics numerically or as trend graphs within WebCTRL
· Supports DIN rail and screw mounting
· Capacitor-backed real-time clock maintains time in the event of a power outage or network interruption for up to three days
· Seamlessly connects to the WebCTRL building automation system.
Programmable BACnet Controller and Router
· Supports MEX and FIO 180 Points Max.
· Universal Inputs and Outputs. No Jumpers.
· OFBBC I/O Bus Option.
· Rnet Sensor & Display Support.
· Remote or DIN Rail Mounting Options.
Hardware Feature
· Enhanced Override Switches ? 0-10VDC Full Scale Input Resolution
· Supports Gig-E, 1000Mbps, BACnet IP, and DHCP IP Addressing
· 100Mbps Ethernet Port for System Boot and Troubleshooting
· Communications Expansion Port for Future Communications Option Cards
· Integration Capabilities to Connect and Manage up to 200 Modbus Points.
· All programs and historical data stored in non-volatile memory, eliminating batteries
· Support for custom control programs created with Automated Logic's EIKON® tool.
· Built-in diagnostics to help operators troubleshoot BACnet network communications
· Ability to capture BACnet network traffic continuously or on demand and save to file.
· Capacitor-backed real-time clock maintains time in the event of a power failure or network interruption
Programmable BACnet Controller and Router
· Supports MEX and FIO 180 Points Max.
· Universal Inputs and Outputs. Not jumpers.
· OFBBC I/O Bus Option.
· Rnet Sensor & Display Support.
· Remote or DIN Rail Mounting Options.
Hardware Feature
· Enhanced Override Switches ? 0-10VDC Full Scale Input Resolution · Supports Gig-E, 1000Mbps, BACnet IP, and DHCP IP Addressing · 100Mbps Ethernet Port for System Boot and Troubleshooting · Communications Expansion Port for Future Communications Option Cards · Integration Capabilities to Connect and Manage up to 200 Modbus Points.
· All programs and historical data stored in non-volatile memory, eliminating batteries · Support for custom control programs created with Automated Logic's EIKON® tool.
· Built-in diagnostics to help operators troubleshoot BACnet network communications · Ability to capture BACnet network traffic continuously or on demand and save to file.
· Capacitor-backed real-time clock maintains time in the event of a power failure or network interruption
These BACnet Advanced Application Controllers (B-AAC) provide a robust solution for single-equipment applications. SE controllers can be used in rooftop units, mechanical rooms, equipment closets, or almost any other airtight location. SE controllers use native BACnet communications over a high-speed 156 Kbps ARCNET or MS/TP network to provide maximum flexibility and interoperability. SE controllers have a large amount of memory for schedules, alarms, trending, and fault detection and diagnostics (FDD)
Key Features and Benefits
· BACnet Advanced Application Controllers (B-AAC) supporting native BACnet communications to field devices over high-speed 156 Kbps ARCNET or BACnet MS/TP networks
· Custom programmable using EIKON® software for the WebCTRL® system, allowing you to create graphical logic sequences for your application.
· Flexible communication port configurations are available for communications to field controllers and routing to other BACnet and non-BACnet devices
· Easy third-party integration using Automated Logic's extensive library of integrations
· Supports OptiPoint™ equipment interfaces
· Supports communicating sensors.
· BACnet Testing Lab (BTL) product listing
· BACnet Protocol Implementation Conformance Declaration (PICS)
Available SE Controllers
SE563/5 DO + 6 UI + 3 AL
SE 6166/6 DO + 16 UI + 6 AL
SE 6104a/6 DO + 10 UI + 4 AL
The Zone Controller line is a fully programmable, native BACnet Advanced Application Controller (AAC) designed to control a single zone in a building. These controllers are suitable for heat pumps, chilled beams, unit fans, and other packaged HVAC applications. They communicate on an EIA-485 LAN using BACnet MS/TP or BACnet over ARCNET communications and seamlessly connect to the WebCTRL® building automation system. ZN controllers have a large amount of memory for schedules, alarms, trending, and fault detection and diagnosis (FDD).
Key Features and Benefits
· BACnet Advanced Application Controllers (B-AAC) supporting native BACnet communications to high-speed ARCNET field devices at 156 Kbps or BACnet MS/TP networks
· Custom programmable using EIKON® software for the WebCTRL® system, allowing you to create graphical logic sequences for your application.
· Flexible communication port configurations are available for communications to field controllers and routing to other BACnet and non-BACnet devices
· Supports OptiPoint™ equipment interfaces
· Supports communicating sensors.
· BACnet Testing Lab (BTL) Product Listing
· BACnet Protocol Implementation Conformance Declaration (PICS)
· Plenum rated.
Available ZN Controllers
ZN551/5 DO+5 UI+1 AL
ZN253/2 DO+5 UI+3 AL
ZN220/2 DO+2 UI+0 AL
La línea de Automated Logic de controladores de equipos grandes son componentes integrales del sistema de automatización de edificios WebCTRL®. Estos controladores tienen la flexibilidad de manejar las aplicaciones de control más exigentes de la industria. Capaces de controlar múltiples equipos al mismo tiempo, estos robustos controladores de construcción BACnet pueden admitir complejas estrategias de control con mucha memoria para programaciones, alarmas, tendencias y detección y diagnóstico de fallas (FDD). Detección de Fallas y Diagnóstico (FDD).
Características clave y beneficios
· BACnet Building Controllers (B-BC) que admiten comunicaciones BACnet nativas a dispositivos de campo a través de TCP / IP, Ethernet, ARCNET de alta velocidad a 156 Kbps o redes BACnet MS / TP
· Programable a medida utilizando el software EIKON® para el sistema WebCTRL®, lo que le permite crear secuencias lógicas gráficas para su aplicación.
· Las configuraciones flexibles de puertos de comunicación están disponibles para comunicaciones a controladores de campo y enrutamiento a otros dispositivos BACnet y no BACnet
· Fácil integración de terceros usando la extensa biblioteca de integraciones de Automated Logic
· Entradas y salidas universales con anulación manual automática
· Admite hasta cinco módulos de expansión de E / S en una configuración de panel de pila o montado a distancia de hasta 100 pies para soluciones escalables
· Admite interfaces de equipos OptiPoint ™
· Soporta sensores de comunicación.
· Listado de productos de BACnet Testing Lab (BTL)
· Declaración de conformidad con la implementación del protocolo BACnet (PICS)
Controladores ME disponibles
ME012u - Multi-equipo, 12 entradas
ME812u - Equipos múltiples, 8 UO, 12 UI
ME812u-E - Equipos múltiples, 8 UO, 12 UI, puerto Ethernet
ME812u-LGR - Enrutador BACnet con 200 puntos de terceros, E / S ampliable, 8 UO, 12 UI
Actuation controllers are fully programmable, native BACnet advanced application controllers that provide zone-level air quality and temperature control for pressure-independent VAV applications. Sophisticated pre-engineered control algorithms reduce energy consumption, extend actuator life, and increase occupant comfort. It communicates on an EIA-485 LAN using BACnet MS/TP or BACnet over ARCNET communications and seamlessly connects to the WebCTRL® building automation system.
Key Features and Benefits
· BACnet Advanced Application Controllers (B-AAC) supporting native BACnet communications to field devices over high-speed 156 Kbps ARCNET or BACnet MS/TP networks
· Separable actuator with a torque rating of 45 in-lbs (5 Nm) that can be mounted up to a maximum distance of 300 ft from the controller
· Precision differential pressure sensor and advanced VAV algorithm increase occupant comfort at minimum and maximum design airflows while extending actuator life
· Custom programmable using EIKON® software for the WebCTRL® system, allowing you to create graphical logic sequences for your application
· Flexible communication port configurations are available for communications to field controllers and routing to other BACnet and non-BACnet devices
· Supports OptiPoint™ equipment interfaces
· Supports communicating sensors.
· BACnet Testing Lab (BTL) Product Listing
· BACnet Protocol Implementation Conformance Declaration (PICS)
ZASF-A | Detachable VAV Damper
The ZASF-A is a secondary VAV damper designed specifically for VAV terminal box applications and is intended for use with the ZN341A and ZN141A. It mounts directly to the secondary shaft of the VAV damper and provides an integral actuator and second integrated flow sensor for damper positioning and airflow sensing in dual-duct or tracked systems.
Flexible and scalable integration platform
Logic® OptiFlex™ Virtual Integrator
The platform connects and monitors large volumes of data
to multiple building systems, subsystems and building devices
- regardless of manufacturer This data is then seamlessly
integrated into the building automation system's WebCTRL®
system, allowing operators to monitor their entire building
systems using a single web-based user interface.
The Virtual Integrator platform runs on a single server
computer (sold separately) and monitors up to 50,000
BACnet™/IP and Modbus® TCP/IP points.
Application Features
• Designed to address HVAC applications including complex
central plants
• Graphically programmed through EIKON® programming
software, an object-oriented tool that provides complete
flexibility for any custom control sequence
• Supports automated logic communication sensors,
available in a variety of zone sensing combinations, and
supports setpoint adjustments and occupancy overrides
• Allows live views of control logic, which uses
real-time operational data and aids in optimizing and
troubleshooting system operations
BACnet Features
• BTL certified and conforms to the following device profiles:
• BACnet Building Controller (B-BC)
System Benefits
• Seamlessly connects to the WebCTRL building automation system
• Multiple serial communication ports to route and
share data across a wide range of building subsystems
BACnet Features hardware
• Supports Gig-E, 1000Mbps, BACnet IP, and DHCP IP addressing
• Locally accessible 100Mbps Ethernet port for system startup
and troubleshooting
• Supports up to 9 FIO expanders in panel configuration or
remotely mounted for scalable solutions (224 total I/O)
• Provides direct connection for power and communication for up to
7 FIO expansion modules when using a DC power supply
• All programs and historical data stored in non-volatile memory,
eliminating the need for batteries
• Capacitor-backed real-time clock maintains time in the event of power
failure or network interruption for up to three days
• Communications expansion port for future communications
optional cards
• Supports 200 Modbus points for system integrations
• Supports up to 16 Act Net communication devices
• USB port for local device upgrades
• DIN rail or screw mounting
Programmable Building Controller
The BACnet Logic® OptiFlex™ Automated Building Controller is a high-performance, native BACnet direct digital controller. As a component of the WebCTRL® building automation system, this controller provides comprehensive control of connected equipment.
The OptiFlex BACnet Building Controller provides the speed, power, memory, and I/O flexibility needed for the most demanding control applications in the industry. Capable of controlling multiple pieces of HVAC equipment simultaneously, this rugged BACnet controller can support complex control strategies.
Application Features
• Designed to address HVAC applications including complex central plants
• Graphically programmed through EIKON® programming software, an object-oriented tool that provides complete flexibility for any custom control sequence
• Supports automated logic communication sensors, available in a variety of zone sensing combinations, and supports setpoint adjustments and occupancy overrides
• Allows live views of control logic, which uses real-time operational data and aids in optimizing and troubleshooting system operations
BACnet Features
• BTL certified and conforms to the following device profiles:
• BACnet Building Controller (B-BC)
System Benefits
• Seamlessly connects to the WebCTRL building automation system
• Multiple serial communication ports for routing and sharing data across a wide range of building subsystems
Hardware Features
• Supports Gig-E, 1000mA addressing Mbps, BACnet IP, and DHCP IP
• Locally accessible 100Mbps Ethernet port for system startup and troubleshooting
• Supports up to 9 FIO expanders in panel configuration or remotely mounted for scalable solutions (208 I/O total)
• Provides direct connection for power and communication for up to 7 FIO expansion modules when using a DC power supply
• All programs and historical data stored in non-volatile memory, eliminating the need for batteries
• Capacitor-backed real-time clock maintains time in the event of power failure or network interruption for up to three days
• Communications expansion port for future communication option cards
• Supports 200 Modbus points for system integrations
• Supports up to 16 ActNet communication devices
• USB port for local device upgrades
• DIN rail or screw mounting
Programmable Building Controller
The BACnet Logic® OptiFlex™ Automated Building Controller is
a high-performance BACnet native direct digital controller. As
a component of the WebCTRL® building automation system,
this controller provides comprehensive control of connected
equipment.
The OptiFlex BACnet Building Controller provides the speed,
power, memory, and I/O flexibility needed for the most
demanding control applications in the industry. Capable of
controlling multiple pieces of HVAC equipment simultaneously,
This robust BACnet controller can support complex control
strategies
Application Features
• Designed to address HVAC applications including complex central plants
• Graphically programmed through EIKON® programming software, an object-oriented tool that provides complete flexibility for any custom control sequence
• Supports automated logic communication sensors, available in a variety
of zone sensing combinations, and supports setpoint adjustments and occupancy overrides
• Allows live views of control logic, which uses real-time operational data and aids in optimizing and troubleshooting system operations BACnet Features
• BTL certified and conforms to the following device profiles:
• BACnet Building Controller (B-BC)
System Benefits
• Seamlessly connects to the WebCTRL building automation system
• Multiple serial communication ports to route and share data on a single device wide range of building subsystems
Hardware Features
• Supports Gig-E, 1000Mbps, BACnet IP, and DHCP IP addressing
• Locally accessible 100Mbps Ethernet port for system startup and troubleshooting
• Supports up to 9 FIO expanders in panel configuration or remotely mounted for scalable solutions (224 I/O total)
• Provides direct connection for power and communication for up to 7 FIO expansion modules when using a DC power supply
• All programs and historical data stored in non-volatile memory, eliminating the need for batteries
• Capacitor-backed real-time clock maintains time in the event of power failure or network interruption for up to three days
• Communications expansion port for future communications, optional cards
• Supports 200 Modbus points for system integrations
• Supports up to 16 Act Net communication devices
• USB port for local device upgrades
• DIN rail or screw mounting
Programmable Building Controller
The BACnet Logic® OptiFlex™ Automated Building Controller is
a high-performance BACnet native direct digital controller. As
a component of the WebCTRL® building automation system,
this controller provides comprehensive control of connected
equipment.
The OptiFlex BACnet Building Controller provides the speed,
power, memory, and I/O flexibility needed for the most
demanding control applications in the industry. Capable of
controlling multiple pieces of HVAC equipment simultaneously,
This robust BACnet controller can support complex control
strategies
Application Features
• Designed to address HVAC applications including complex central plants
• Graphically programmed through EIKON® programming software, an object-oriented tool that provides complete flexibility for any custom control sequence
• Supports automated logic communicating sensors, available in a variety of zone sensing combinations, and supports setpoint adjustments and occupancy overrides
• Allows live views of control logic, which uses real-time operational data and aids in optimizing and troubleshooting system operations
BACnet Features
• BTL certified and conforms to the following device profiles:
• BACnet Building Controller (B-BC)
• BACnet BBMD (B-BBMD)
• Supports BACnet External Device Registration (FDR)
• Supports BACnet interoperability with and between BACnet IP, BACnet MS/TP, and BACnet over ARC156
Hardware Features
• Supports Gig-E, 1000 Mbps, BACnet IP, and DHCP IP addressing
• Locally accessible 100 Mbps Ethernet port for system startup and troubleshooting
• Supports up to 9 FIO expanders in panel configuration or remotely mounted for scalable solutions (224 I/O total)
• Provides direct connection for power and communication for up to 7 FIO expansion modules when using a DC power supply
• All programs and historical data stored in non-volatile memory, eliminating the need for batteries
• Capacitor-backed real-time clock maintains time in the event of power failure or network interruption for up to three days
• Communications expansion port for future communication option cards
• Supports 200 Modbus points for system integrations
• Supports up to 16 Act communication devices Net
• USB port for local device updates.
• DIN rail or screw mounting
System Benefits
• Seamlessly connects to the WebCTRL building automation system
• Multiple serial communication ports for routing and sharing data across a wide range of building subsystems
APPLICATION AND USE
The fully programmable FCU controller is built with the aim of controlling fan control units. The controller is factory-equipped with
the two most popular open communication protocols, Modbus RTU/ASCII and BACnet MS/TP, which are selected via DIP switches.
To minimize time and simplify the commissioning process, the controller is delivered with a default application, which supports the
most popular types of FCU. A dedicated DIP switch allows the application parameters to be adjusted. Furthermore, in BACnet
protocol, the application has a built-in function that allows automatic linking of master and slave controllers in groups (20 groups on
the bus, up to 6 devices in one group).
If the default application does not meet the project requirements, it can be modified or created from scratch using the free software
ISMA tool. It is possible to change the application in real time via USB.
There are three hardware versions with different types of triac outputs and power supply.
FEATURES
• Universal default application
• Support for 2 or 4 pipe systems
• Application adjustable by dedicated DIP switch
• Addressing from 0 to 254 by DIP switch
• Sedona Framework 1.2 support
• iSMA tool – free programming software
• Connection to higher level system with Modbus RTU/ASCII
or BACnet MS/TP
• mini USB to manage the application (provides power)
• Real-time programming
• 18 built-in inputs/outputs
• Fast processor with ARM core
• 2 RJ12 (1 RS485) for wall panel connection
• Built-in 24V AC for external equipment (230V AC version)
• Easy firmware management, backup and restore with FCU upgrade software
Room Application Controller
IP Room and Zone Management
The RAC18-IP controller is a multi-functional device that provides
comfort in a single room or zone of the building. Onboard
18 I/Os with serial and Ethernet ports, and additional
extension cards make the controller a versatile system for
comfort management, light and blinds control, integration, and
monitoring.
Cutting-edge technology at the edge
The powerful IoT-ready nano EDGE engine enables
capabilities, for a microcontroller-based device. Take advantage of
time-saving automatic BACnet exposure, real-time
programming, and cloud connectivity.
Openness and reliability
Take advantage of IP connectivity with open protocols such
as MQTT, BACnet, Modbus, and ensure maximum energy efficiency
for your building with any monitoring system.
RAC18-IP controllers are protected by a unique fail-safe
on each Ethernet port to provide maximum reliability.
Flawless Programming and Maintenance
Maintain and program your device from anywhere in real-time
with a free, dedicated tool. Easy replacement process
with a removable SD card-based system and user data.
18 Inputs and Outputs
4 Universal Inputs
Support for over 20 types of temperature
sensors and voltage, resistance, current, and
dry contact measurements on each universal
input.
4 Digital Inputs
Dry contact inputs – made for monitoring.
Fast 100 Hz pulse counter with override
Function saves real-time values to the
EEPROM memory.
3 Analog Outputs
0-10V DC control with 10mA accuracy, PWM
modes, and a maximum load of up to 20mA
to power external relays make the output
suitable for a variety of scenarios.
5 Digital Outputs
Equipped with 3A normally open relays allow
for direct control without additional relays.
2 triac outputs
Triac outputs dedicated to heating and
thermal cooling valve actuators.
Multi-protocol module with a MIX of I/O
The most versatile I/O module with 18 or 38 inputs and
outputs, offering the most cost-effective price per point ratio.
The most popular types of inputs and outputs are MIXED in one
Space-saving design that allows the module to be a versatile
controller extension, whether in a small or large installation.
Open protocol standard
Powerful I/O modules that function as remote or distributed I/O
OS over IP with open protocols: BACnet IP and Modbus TCP/IP. The open protocol standard offers versatility of installing the modules
in both new and existing installations, whether a system expansion or an upgrade.
Daisy chaining
Two Ethernet ports operating in a switch mode allow multiple modules to be
daisy chained together via an RJ45, improving the wiring process and reducing engineering time.
IP I/O Module and Modbus Gateway
Each IP I/O module, in addition to its functionalities, is equipped
with a COM1 communication port that serves as a Modbus TCP/IP to Modbus RTU/ASCII gateway.
BACnet IP Communications
Multiprotocol I/O modules are equipped
with Building Automation and Control
Networks (BACnet) and are certified by
BACnet Official Test Laboratories (BTL).
ModbusTCP/IP
Modbus is one of the most widely used protocols
in industrial electronic devices.
Modbus TCP/IP to Modbus RTU/ASCII
Gateway
Multiprotocol IP I/O modules can serve as
a Modbus gateway with an integrated COM1
port.
Key Features and Functionalities
BACnet and Modbus protocols, easily
selectable with a DIP switch.
·Embedded web server for I/O and network
configuration.
·Up to 38 inputs and outputs to suit most building
applications.
·Integrated LED statuses for all I/O and
communication.
·Integrated Modbus TCP/IP to Modbus RTU/
ASCII gateway.
·Two Ethernet ports operating in switch mode.
BACnet MS/TP and Modbus RTU
The RS485 multi-protocol I/O modules are equipped with two
popular open protocols in building automation, BACnet and
Modbus.
Seamless Configuration
The protocol and other parameters can be set in a
matter of seconds thanks to the integrated rotary and DIP switches.
USB Powered
The ability to be powered from a USB port facilitates easy
testing and an easy upgrade process.
iSMA Configurator
Portable software dedicated to device configuration and
firmware upgrade.
Dedicated Niagara Framework Modules
Seamless integration of multi-protocol I/O into the Niagara Framework
using a dedicated module.
Standard Inputs and Outputs
Universal Inputs
Support for over 20 types of temperature
sensors and voltage, resistance, current and
dry contact measurements on each universal
input.
Digital Inputs
Dry contact inputs – made for monitoring. 100 Hz
Fast pulse counter with override function
saves real-time values in EEPROM
memory.
Analog Outputs
0-10 V DC control with 10 mA accuracy, PWM
modes and a maximum load of up to 20 mA
for powering external relays makes the output
suitable for a variety of scenarios.
Digital Outputs
Equipped with normally open 3A relays allow
for direct control without additional relays.
Future-proof I/O modules
Make a building future-proof with open communication protocols!
The modules can be integrated with most modern BMS systems.
The IP I/O modules are equipped with integrated Modbus TCP/IP and
BACnet IP. The RS485 I/O modules have integrated Modbus RTU/
ASCII and BACnet MS/TP.
Modules suitable for small and large applications
Extremely compact dimensions and a wide range of I/O
combinations make the MINI modules applicable in most building automation
systems.
Perfect configuration
The protocol and other parameters can be set in a matter of
seconds thanks to the integrated rotary and DIP switches.
IP I/O modules and Modbus gateway
Each IP I/O module, in addition to its functionalities, is equipped with
a COM1 communication port that serves as a Modbus TCP/IP to
Modbus RTU/ASCII gateway.
Key Features and Functionalities
Wide range of I/O modules
Compact size and a wide range of module
types allow maximum flexibility in projects.
Integrated HVAC and light applications
Configurable light, cooling and heating
algorithms make the module applicable as
standalone controllers.
Manual override switches
Each output can be manually overridden using
a dedicated manual operation switch.
Modbus TCP/IP to Modbus RTU/ASCII gateway
Modbus gateway integrated into the COM1 port
allows integration of up to 128 Modbus slave devices
to the IP layer.
Manual Override Switches
Modules with digital, triac and analog outputs can be manually
overridden using manually operated switches.
Standalone Controllers
HVAC and lighting applications integrated into selected modules
make them applicable as standalone controllers in light,
cooling and heating applications.
Embedded Web Server
Technical Overview and Troubleshooting. BBMD, I/O and
protocol configuration – all can be done with an integrated web
server.
High Scalability
RS485 I/O modules use only ¼ UL (unit load) on the bus.
It means that 128 iSMA I/O modules can be used on one serial bus,
according to EIA-RS485.
Quality Tested by Certificates
Both hardware construction and communication quality are
certified by external entities – Underwriters Laboratories – UL,
BACnet—BTL Test Laboratories.
Interruptores de anulación manual
Los módulos con salidas digitales, triac y analógicas pueden ser manualmente
anular usando interruptores de operación manual.
Controladores independientes
Aplicaciones de HVAC e iluminación integradas en módulos seleccionados
hacerlos aplicables como controladores independientes en la luz,
aplicaciones de refrigeración y calefacción.
Servidor web incorporado
Resumen técnico y solución de problemas. BBMD, E/S y
configuración de protocolo: todo se puede hacer con una web integrada
servidor.
Alta escalabilidad
Los módulos de I/O RS485 usan solo ¼ de UL (carga unitaria) en el bus.
Significa que se pueden usar 128 módulos de I/O iSMA en un bus serie,
según EIA-RS485.
Calidad Comprobada por Certificados
Tanto la construcción del hardware como la calidad de la comunicación son
certificado por entidades externas – Underwriters Laboratories – UL,
Laboratorios de pruebas BACnet—BTL.
Módulos de I/O Modbus delgados
La línea S consta de módulos delgados que ofrecen de 6 a 16 entradas y salidas
en 12 combinaciones. Debido a su tamaño, se pueden instalar varios módulos.
instalado sin ocupar mucho espacio en los armarios de control. Cada
módulo está equipado con un optoaislador entre las entradas/salidas, fuente de alimentación y RS485.
Protocolos de comunicación abierta
Cada módulo SfAR I/O tiene Modbus RTU/ASCII integrado
admite hasta 128 módulos en el bus RS485. También hay una
posibilidad de integrarlos en una red Modbus TCP/IP gracias
al dispositivo SfAR-S-ETH dedicado, un módulo de puerta de enlace que permite
integración de la red Modbus RTU en una red Modbus TCP/IP.
Operación confiable
Las entradas y salidas de los módulos de I/O SfAR están aisladas de la alimentación
alimentación y puerto RS485 mediante optoaisladores para evitar interferencias en
bucles de señal.
Sistema de conector rápido
Para simplificar la instalación, los módulos han sido equipados con
el sistema Quick Connector usando un cable SfAR-S-LINK dedicado
permite la conexión de hasta 10 módulos, que proporcionan tanto
Comunicación RS485 y fuente de alimentación externa.
The smallest distributed I/O modules
The 1M line consists of small modules with a small amount of
I/O – 7 types of modules with 2 to 4 I/O. Each module with
an opto-isolation between I/O, power supply and RS485
on board is a perfect choice for distributed systems with
devices dispersed over a large area.
Made to control and communicate
Each module in this line is created for a specific purpose with
one main goal: to connect devices without Modbus on board
on the Modbus network.
Easy setup and commissioning
The module is equipped with a set of LEDs that are used to indicate
the status of I/O, power supply and RS485 communication.
Configuration of the modules is done with our free
software, the SfAR configurator. An integrated mini USB allows
to perform a primary configuration of the unit without
an additional power supply.
SfAR-1M-1AI1DO
The module can be used not only as an
I/O extension of the controller, but also as a
standalone application controller.
The perfect solution for controlling lights,
level according to light measurement,
and other similar applications.
1 analog input and 1 digital output
The analog input can operate in 7 modes as
a voltage or current input. One digital
output is an NPN transistor output.
opto-isolation
The inputs and outputs are isolated from
logic with opto-isolators.
These sensors provide the function and flexibility you need to manage conditions important to the comfort, productivity, and sustainability of your facility, and are designed to work with ZN, SE, and ME line controllers.
ZS sensors measure ambient temperature, relative humidity, carbon dioxide, motion, and VOCs (volatile organic compounds), and are available in a variety of zone sensing combinations to meet your specific control requirements.
Wireless sensors work in conjunction with a wireless adapter, which enables wireless communication between the wireless sensors and a BACnet WebCTRL® controller in the space. By wirelessly sensing temperature and humidity, our WebCTRL controllers can make intelligent decisions to optimize control of heating and cooling systems in the building, providing optimal comfort and energy efficiency for occupants.
Key Features and Benefits
· EnOcean® Wireless Technology – No batteries required when there is sufficient ambient light to power the sensor
· Smart Monitoring – Key sensor statuses are monitored and shared with the WebCTRL system for intelligent alarms, fault detection and diagnosis, and proactive maintenance
· Capacitor charge backup (5 days)
· Sensor signal strength (up to 24m with optimal position)
· Heartbeat – detects when a sensor goes offline
· Designed to co-exist on Rnet with Automated Logic’s wired ZS sensors
· Single zone controllers can support a total of 5 sensors
· Multi-zone controllers support up to 15 sensors.
· Robust and reliable communications through walls and minimal obstructions up to 80’ from the wireless adapter
· Easy to install
· Wireless software included for quick and easy commissioning
· Global compatibility
· Will be available in different frequencies for different parts of the world
· Supports English and metric units
· Sensing capability
· Temperature only option
· Temperature and relative humidity option.
· Temperature via remote thermistor (sold separately), as a remote temperature probe for chiller or duct uses, as well as the NSB line button, flush wall, and outdoor temperature sensors.
· Averaged Duct Temperature Sensors
· Carbon Monoxide Sensors
· Clamp Temperature Sensor
· CO2 Duct Sensors
· Compact Low Pressure Sensors
· Compact Pressure Sensors
· Duct Temperature and Humidity Sensors
· Duct Temperature Sensors
· Immersion Temperature Sensors
· Low Profile Button Sensors
· Low Profile Pressure Pickup Port
· Outdoor Air Static Pressure Pickup Port
· Outdoor Air Temperature and Humidity
· Refrigerant Leak Detector
· Remote Temperature Probes
· Static Pressure Probe Assembly
· Belt Temperature Sensors
· Thermobuffel Temperature Sensors
· Thermostat Guard
· Voltage Converter
· Wall Plate Temperature Sensors
· Water Leak Detector
· Zone Pressure Pickup Ports
BACnet Thermostat
OptiPoint™ BACnet Plus thermostats feature a contemporary design, large backlit LCD display and intuitive controls, allowing occupants to easily control their comfort. These thermostats offer control of a building’s heating, ventilation and air conditioning (HVAC) system from within a facility, or from any BACnet-compatible building management system (BMS), including WebCTRL®.
APPLICATION AND USE
The Touch Point is a modern comfort management wall panel with the two most popular open communication protocols:
Modbus RTU/ASCII and BACnet MS/TP. The Touch Point is available in different sensor configurations (temperature, CO2 and
humidity), colours, versions with or without display and touch buttons. The panel can be configured using the iSMA configurator
software or Modbus registers/BACnet objects. It fits into most standard junction boxes in Europe and can be easily installed with a wall back box.
FEATURES
• Modern and intelligent design
• Intuitive management
• Easy installation and configuration
• Multi-protocol interface
• Maximum flexibility
• Free software: iSMA Tool and iSMA Configurator
• Five touch function buttons
• RS485 interface
• Modbus RTU/ASCII and BACnet MS/TP
• Temperature sensor as standard, humidity and CO2 sensors as an option
• USB Type-C interface
• DIP switches for configuration
• Buzzer
• RGB LED navigation
Intuitive Management
LP panels interact with a user with a 2.3” LCD display that indicates a device’s
operating status and shows real-time measurements from sensors. Four function buttons allow setting the desired
parameters.
Unlimited Configuration Possibilities
The panels are equipped with a special group of Modbus registers and
BACnet objects that the user can use to view and
control lights, blinds, alarms and set occupancy statuses.
Ease of Installation and Configuration
Suitable for surface and flush mounting, the LP panel offers effortless
configuration using network protocols or a built-in USB port, even
without external power supply.
Maximum Flexibility
LP panels are available with a set of temperature, CO2 and humidity